Fuse Distribution Panel

Newmar's GMT Fuse DC Distribution Panels models FDP-1010 and FDP-2020 image.

These fuse panels are ideal for DC distribution to low power loads in 24 and 48 volt positive and negative ground network applications and provide enhanced system reliability via dual input buses which allow configuration with redundant power sources. Each input bus accommodates 10 or 20 GMT output fuses (depending on model) in ratings up to 15 amps. Form C alarm contacts provide remote monitoring of input power and blown fuse conditions. Front panel LEDs indicates normal operation, fuse failure mode, as well as a user configured external alarm signal. Their low profile 1.75” (1 RU) occupies minimal space and can be configured for 19 or 23 inch rack mounting.

 

Model Nominal
Input/Output
Total Fuse
Capacity
Amps per Bus
(Dual Bus)
Total Current
Capacity
FDP-1010 +/- 24 or 48 VDC 20 100 200A
FDP-2020 +/- 24 or 48 VDC 40 100 200A


Download a GMT Fuse DC Distribution Panel PDF Data Sheet


Features

  • GMT Fuse
  • Form “C” alarm contacts
  • Polarity insensitive panels work with positive and negative ground systems -/+ 24 or -/+ 48 VDC
  • 1RU (1.75”) in height will configure to 19” or 23” rack mounting

Operating Temperature

-20° to +60° C
-5° to + 140° F

Compliances

NEBS 3 certified

Mechanical

  • Steel case painted flat black with white graphics
  • Mounting ears provided for 19” and 23” rackmount, flush mount or 6” offset
  • 1 RU (1.75”), can be zero clearance mounted directly adjacent to other equipment

Front Panel Details

LED status indicators:
Normal Operation
Fuse Alarm
External alarm
Easy accessible fuse blocks
Spare fuse holder

Alarms

  • Form C alarm contacts for each bus
  • External ground input alarm (bay or rack alarms)

Specifications

Nominal Input/Output: +/- 24 or +/- 48 VDC
Total Fuse Capacity:
FDP 1010 - 10 GMT fuses per bus
FDP 2020 - 20 GMT fuses per bus
Total Current Capacity:
FDP 1010: 200 amps (dual 100 amp bus)
FDP 2020: 200 amps (dual 100 amp bus)
Fuse Holder & Fuse Rating:
15 amps max.

GMT Fuses

Available amperages: 1, 3, 5, 10, 15 Other ratings available upon request
Note: Fuses sold separately

Rear Panel Details

Input Terminal Block: Two 1⁄4” studs on 5/8” centers
Output and Alarm Terminal Blocks:
FDP 1010: Barrier Terminal Block; #22 to #10 AWG wire for fork or ring #6 screw
FDP 2020: Elevator clamp style terminal block; #26 to #12 AWG wire.
Cable Management Bar Clear Lexan cover protects wiring connections

Case Size

Inches Centimeters
H W D H W D
1.75 17 11.5 4.5 43.2 29.2
Weight: 8 pounds


Request a GMT Fuse DC Distribution Panel Evaluation Sample