Hot Swap Rectifiers
150 Watt Rectifiers
   ULM-100
600 Watt Rectifiers 1.8kW
1000-2000 Watt
Rectifiers 6kW
2000 Watt Rectifiers, 14kW
Rackmount Rectifiers
Power Modules
Integrated w/ built-in battery
Power Function Manager
ULM-100
DC-DC Converters
Rackmount
Mobile Mount
DC-AC Inverters
Rackmount
Mobile Mount
Power Distribution
Circuit Breaker
Fuse
DST-FB
Power Distribution System
Battery Chargers
Wall Mount
12, 24, 32 V; 8-95 Amps
Wall Mount Modular
12, 24 V; 67-100 Amps
Mobile Mount
12, 24 V; 8-35 Amps
Power Plants
DC Power Plants
Rackmount Power
Accessories
Rack Accessories
Trays & Shelves
Remote Monitoring
Site Power Monitor
Batteries & Accessories
Battery Modules
Batteries
Battery Trays & Shelves
Integrators & Isolators
Instruments/Analyzers
Automatic Power Selector
Power Supplies
Mobile Mount
With built-in battery
Enclosure Power System
Pole or Wall Mount
Site Power System
RR Site Power System
Low Voltage Disconnects
Rackmount
Wall Mount
Disconnect Timer
Mobile DC UPS
StartGuard & Nav-Pac

Mobile Data Power System

DC Power Conditioners
12 & 24 Volt Stabilizers
Noise Filters
Accessories
Digital Meters
Communication
Electrical Installation
Phone Coms
Paging Speakers
Waterproof radio covers

Click Here To Download
A PDF Version Of Our
Product Catalog

Newmar © 2010

Integrated Power Systems

Newmar’s Powering the Network with a Integrated Power System (IPS) is a unique multifunction power supply which incorporates built-in battery back-up and numerous power accessories within a single 2RU (3.5") chassis

The Integrated Power System (IPS) is a unique multifunction power supply which incorporates built-in battery back-up and numerous power accessories within a single 2RU (3.5") chassis, thus eliminating time-consuming system integration, component sourcing and installation, while saving precious rack space--ideal for any low-to-medium power application requiring AC fault tolerant operation.

A precision regulated power supply/charger, back-up battery, low voltage battery disconnect, output metering, LED status and Form C alarm contacts are all pre-wired and calibrated within the unit for plug-and-play operation. Plug-in terminals are provided for easy wiring of an additional parallel rectifier input, or external batteries for increased back-up capacity.

The batteries are always in-line with the load, thus there is no interruption from relays or transfer switches in the event of AC loss. Batteries are recharged when AC is restored. A manual battery disconnect switch allows internal or external battery service or replacement while the system is running. Models available for -48, +24 and +12 volt applications.


Features
• Precision regulated power supply simultaneously maintains batteries at peak charge and supplies
  system load.
• Built-in batteries instantly power load during AC failure--no switch-over delay. 3-5 year average life.
  Terminals provided for additional external batteries for increased back-up capacity.
• Terminals provided for easy addition of parallel rectifier. (48V and 24V models only)
• Automatic low voltage and manual battery disconnect.
• Numerous front panel monitors--L.E.D. status indicators and digital ammeter/voltmeter.
• Form C summary failure alarm contacts; loss of internal rectifier output, loss of external rectifier
  output, LVBD contactor open. AC input failure alarm contacts optional.
• Numerous protection features--AC input breaker, internal battery breaker, auto thermal
  shutdown/recovery,  current-limiting, short-circuit and over-voltage protection.
• 19" or 23", 6” forward rackmount brackets provided

Specifications
Model Input Amps
@ Full Load
115 / 230
Output
Internal
Battery
Capacity
Ground
Reference
Ground
Reference
VDC Adjustment
Range
Supplemental
Input Port*
IPS 48-11 11 / 5.5 54.4 40-60 VDC 40 Amps 5 A-H Positive Positive
IPS 24-22 11 / 5.5 27.2 20-30 VDC 40 Amps 10 A-H Negative Negative
IPS 12-40 11 / 5.5 13.6 10-15 VDC N/A 20 A-H Negative Negative

AC Input
Input Range (switch selectable):
115V = 92-130 VAC
230V = 184-260 VAC
Frequency: 47-63 Hz

DC Output
Voltage/Amperage: See Matrix above
Maximum Load with External Rectifier and Battery Inputs: 40 amps
Regulation: Line: ± 1 %, Load: ± 2 %
Ripple: ± 1 %

Power Scaling via Back Panel Quick Connects
External Rectifier Input: 24V, 48V only; 560 or 1,000 watt (see PM Series)
External Battery Bank: 12V/24V/48V

Environmental
Temperature Rating: -10° to + 60° C; Derate linearly from 100% load @ 50° C to 75% @ 60° C

Mechanical
Chassis: Aluminum
Rack Size: 19" or 23", 2 RU (3.5")
Cooling: Forced Air
Dimensions: 3.5"H x 17"W x 18"D
Weight: 33 Lbs. (with batteries), 17 Lbs. (without batteries)

Protection
• Current Limit, Short Circuit
• Over Voltage
• Auto Thermal Shutdown/Recovery
• Input Fuse and Circuit Breaker
• Circuit Breaker For Internal Battery
• Low Voltage Battery Disconnect (Adjustable)

Internal Batteries
Type: 12 Volt, 5 A-H Sealed Lead-Acid, Maintenance-Free
Amp-Hour Capacity: See Matrix below
Weight: 4 Lbs. each; 4 Batteries per Unit
Approvals: UL Recognized, DOT and IATA, approved for shipment by air

Internal Battery
Constant Current Performance (Amps) to 1.75 VPC
MODEL 5 MIN. 15 MIN. 30 MIN. 1 HR. 2 HRS.
IPS 48-11 15.0 8.0 5.0 3.0 2.0
IPS 24-22 30.0 16.0 10.0 6.0 4.0
IPS 12-40 40.0 32.0 20.0 12.0 8.0

Indicators and Alarms
System "Nominal" indicator lights:
• AC OK
• External Rectifier ON/OK*
  *Except IPS-12-40
• Internal Rectifier On/OK
• Battery Contactor Closed
System "Warning" indicator lights:
• Check System
• Battery Disconnected
Form C Alarm Contacts:
• Summary Failure
• AC Input Failure (Optional)

Top View With Cover Removed



Options
AC Input Fail Contacts - Specify 115 or 230 VAC
Rectifier/Battery Input Cable Assembly (Model CA-24)
Rear Support Bracket for Flush Mounting Models: RSB-19 or RSB-23
Distribution Panel Models: DST-10 (UL), DST-20A (UL)
Unit Supplied Without Batteries



Request Evaluation Sample